Staff
recommends that the Preliminary Plat be continued to the May 3, 2004
City Council meeting as the stipulations of approval have not been
met.
PLANNING COMMISSION RECOMMENDATION:
Planning Commission recommended that the Preliminary Plat
be approved with the following stipulations:
1. Prior to Preliminary Plat approval
by the City Council, a revised grading plan shall be submitted for
review and approval;
2. Prior to Preliminary Plat approval by the City Council, a revised
drainage plan shall be submitted for review and approval. In addition,
the plat shall be revised to show drainage easements as needed;
3. Prior to Preliminary Plat approval by the City Council, the plat
document shall be revised showing a ditch easement for the South Side
Ditch;
4. Prior to Preliminary Plat approval by the City Council, a utility
master plan shall be submitted for review and approval. In particular,
the utility master plan shall provide for the extension of utilities
through the subject property as well as to adjacent properties;
5. Prior to Preliminary Plat approval by the City Council, sewer plans
prepared by a Registered Professional Engineer showing the extension
of sanitary sewer mains and service lines shall be submitted for review
and approval. If an on-site waste-water system is proposed, then a
plan prepared by a Registered Professional Engineer shall be submitted
for review and approval;
6. Prior to Preliminary Plat approval by the City Council, water plans
prepared by a Registered Professional Engineer showing the extension
of water mains shall be submitted for review and approval. If a shared
well is proposed than it shall be designed as a public water system
or a Variance to the Subdivision Regulations shall be obtained. In
addition, the plat document shall be revised to show utility easement(s)
as needed
7. Prior to Preliminary Plat approval by the City Council, complete
engineering plans as specified in Section 16.20.040 of the Rapid City
Municipal Code shall be submitted for review and approval. In particular,
complete street design plans shall be submitted showing the location
of utilities, storm drainage, curb and gutter and sidewalk improvements
for all adjacent and interior roadways. In addition, soil testing
and design calculations for pavement design shall be submitted for
review and approval;
8. Prior to Preliminary Plat approval by the City Council, construction
plans for the north-south street shall be submitted for review and
approval. In particular, the north-south street shall be constructed
as a collector street with a minimum 60 foot wide right-of-way and
a minimum 24 foot wide paved surface, curb, gutter, sidewalk, street
light conduit, water and sewer or a Variance to the Subdivision Regulations
shall be obtained;
9. Prior to Preliminary Plat approval by the City Council, construction
plans for the east-west street shall be submitted for review and approval.
In particular, the east-west street shall be constructed as a collector
street with a minimum 60 foot wide right-of-way and a minimum 24 foot
wide paved surface, curb, gutter, sidewalk, street light conduit,
water and sewer or a Variance to the Subdivision Regulations shall
be obtained;
10. Prior to Preliminary Plat approval by the City Council, all necessary
changes shall be made to the construction plans as identified on the
redlined drawings. In addition, the redlined drawings shall be returned
to the Engineering Division;
11. Prior to Preliminary Plat approval by the City Council, a structural
site plan shall be submitted for review and approval;
12. Prior to Preliminary Plat approval by the City Council, a subdivision
cost estimate shall be submitted for review and approval;
13. Prior to Preliminary Plat approval by the City Council, a fire
hydrant design plan showing the location of fire hydrants and water
lines, including the size of the proposed water lines, shall be submitted
for review and approval or a Variance to the Subdivision Regulations
shall be obtained;
14. All Uniform Fire Code shall be continually met;
15. Prior to submittal of the Final Plat, road names for the two streets
shall be submitted for review and approval. In addition, the plat
document shall be revised to show the approved road names;
16. Prior to submittal of the Final Plat, the property shall be rezoned
from General Agriculture District to allow the proposed 33.4 acre
and the 14.3 acre lot; and,
16. Upon submittal of the Final Plat, surety for any required subdivision
improvements that have not been completed shall be posted and the
subdivision inspection fees shall be paid.
Vote: (9 to 0 with Brannan, Brown,
Henning, Hoffmann, Nash, Prairie Chicken, Schmidt, Stone and Wevik
voting yes and none voting no)
|